The screen of the cable should normally be connected to 0V, ONLY at the   controller and NOT at the detector.
          
          However, if the detector is mounted   on a non-conductive surface, then the detector enclosure should
          be earthed   locally OR through the cable screen.
            
          It is essential that electrical   current does NOT flow in the detector cable screen as may happen if the screen   was earthed at both ends.