2. What cable should I use to connect the CGS500 sensor?


The cable used to connect a CGS500 sensor should be 3-core cable, with stranded copper conductors and an overall screen (shield).

The gauge of cable should be selected to ensure that the cable resistance does not exceed the maximum specified for the controller.

The maximum cable resistance for the Multichannel controller is 10 Ohms per line (i.e. 20 Ohms Loop). The following table will give an indication of maximum cable runs for the Multichannel controller.

Cable size Maximum cable length
0.75mm2 150 metres
1.00mm2 200 metres
1.50mm2 300 metres
2.50mm2 500 metres

The maximum cable resistance for the Single Channel and Four Channel controllers is 4 Ohms per line (i.e. 8 Ohms Loop). The following table will give an indication of maximum cable runs for the Single Channel and Four Channel controllers.


Cable size Maximum cable length
0.75mm2 400 metres
1.00mm2 500 metres
1.50mm2 700 metres
2.50mm2 1200 metres